MC80 Duplex Gas Manifold SystemIntroduction

1.MC80 HP Unit

The MC80 HP Unit includes two regulators with pressure relief valves and is connected to two cylinder banks via high-pressure hoses. When the active cylinder bank is depleted, the system automatically switches to the reserve bank, ensuring an uninterrupted gas supply.

2. MC80 Stabilizer

The stabilizer maintains constant operating pressure in the distribution system. The module is equipped with two regulators featuring pressure relief valves. By reducing gas pressure in two stages, it minimizes pressure drops during cylinder switchovers. Additionally, the unit is designed for easy connection to a liquid oxygen supply tank (LOX).

3. Gas Alarm System - Based on the product variant

GCE's user-friendly gas alarm system boasts simple controls and handy functionalities. It electronically monitors and alerts for high or low distribution pressure, high intermediate pressure issues, leakage from the reserves, and operating side changes. The product is either equipped with an alarm system or a sensor only.

MC80 Duplex Gas Manifold SystemFeatures

Basic Components

MC80 Duplex gas manifold system includes the following components:

  • MC80 HP Unit
  • MC80 Stabilizer
  • Sensors 4-20 mA. Alarm or just sensor based on item in column "Alarm"
  • Evacuating kits for collecting pipe
  • Shut-off valve for the distribution line
  • HP filters

Additional Options

For a complete MC80 Duplex standby manifold add:

  • Collecting pipe set (high-pressure valves and non-return valves, high-pressure components)
  • High-pressure hoses with safety wire
  • Gas name sign
  • Connection pipe 90-degree
  • Extension pipes if needed

MC80 Duplex Gas Manifold SystemGeneral properties

General properties

GasesO2, Air, N2, N2O, CO2
Nominal flow (m3/h)200
TECHNICAL DATA - HIGH PRESSURE UNIT MC80
Inlet nominal pressure (BAR)200 (20 000 kPa)
Outlet nominal pressure12 bar (setting range 10–16 bar)
Inlet connectionW21.8×1/14"M
Outlet connection G3/4"F
Pressure relieve valve 17 bar
Pressure relieve valve pipe dimension∅ 10 mm
Purge valves connection W21.8×1/14"M + pipe ∅ 15 mm
TECHNICAL DATA - STABILIZER MC80
Inlet maximal pressure 20 bar (2000 kPa)
Outlet nominal pressure4,5 bar (setting range 0,5–6 bar)
Inlet connection G3/4"F
Outlet connectionG3/4"F
Pressure relieve valve6,8 bar
Pressure relieve valve pipe dimensionø 15 mm

Configurations

Loading...
... loading table ...

Quality Standards

We comply with all relevant regulations

See our CERTIFICATIONS >

MC80 Duplex Gas Manifold SystemDownloads

Find our Products

Source our products wherever you are

You can have confidence in our global network

Find a distributor
GCE main LogoPart of ESAB Corporation

GCE Group

Turmstrasse 30

6321 Steinhausen

Zug

Switzerland

Copyright © 2024 GCE. All rights reserved.
facebooktwitterlinkedinyoutubeinstagram